We supply lighting to commercial, industrial & residential applications. DLS can provide competitive quotes on any size job involving indoor or outdoor lighting. Also, we specialize in hard to find Lamps, Fixtures and Miniature bulbs.

TITLE 24 INFORMATION



Effective October 1, 2005

Commercial

• Commercial office areas will be limited to a total of 1.2 watts per square foot. There is also a mandatory set aside of 0.2 watts per square foot for task lighting.

• A lighting management system is required for spaces of any square footage with an astronomical timeclock required to control outside luminaires. This includes carports, breezeways, walkways and the like.
 

• Non-conditioned spaces, which previously did not need to comply with Title 24, now have to comply just as conditioned spaces do.
• All exterior lighting is now required to be bi-level (footcandle measurement).
 

• All exterior fixtures are to be a cutoff type.

Residential

• Incandescent sources are required to have dimmers or occupancy sensors.

• Recessed fixtures are required to be air tight and IC rated.

• 50% of the wattage generated in the kitchen must be from a high efficacy (compact fluorescent) source.

• Compact fluorescent fixtures are required to have electronic ballasts if they are 13 watts or greater.

• Bathrooms with occupancy sensors must have a manual on and automatic off.

• Exterior house mounted fixtures must be high efficacy and use a combination photosensor/motion sensor.